logo

BTU Diesel Generator

Sector: Water Supply and Storage • Location: California, United States of America

Source: California Purchasing Group

Tender
Closed

Diesel Generation Specifications RFQ # 1PA400614 BACKGROUND The specifications below detail what is needed for a Diesel Generator . The Diesel Generator is needed by CAL FIRE ’ s Chico Air Attack Base to remain operable during an electrical outage . personnel . ACTION SUBMITTALS • Product Data : For each type of

Status
Closed
Sector
Water Supply and Storage, Energy Storage, Steel, Cement, Geothermal, Manufacturing (Industrial), Oil and Gas, Power Generation (CCGT), Government
Location
California, United States of America
Updated
3 Nov 2026
Source
California Purchasing Group

ConstructChat

Ask ConstructChat about BTU Diesel Generator

Pick a question to edit it, or write your own.

First answer free · no account

I am a

Tender Information FAQ

Tender Information

3 Q
The tender “BTU Diesel Generator” is a tender record in Taiyo, linked to the Water Supply and Storage sector. It is issued for works, goods, or services related to California, United States of America.

Participants

Not available for this record.

Status

Original status

closed

Taiyo status

Closed

Taiyo last update

2026-11-03

Contact

Not available for this record.

Description

Description

Diesel Generation Specifications RFQ # 1PA400614 BACKGROUND The specifications below detail what is needed for a Diesel Generator . The Diesel Generator is needed by CAL FIRE ’ s Chico Air Attack Base to remain operable during an electrical outage . personnel . ACTION SUBMITTALS • Product Data : For each type of product . • Include rated capacities , operating characteristics , electrical characteristics , and furnished specialties and accessories . • Include thermal damage curve for generator . • Include time - current characteristic curves for generator protective device . • Include fuel consumption in gallons per hour ( liters per hour ) at 0 . 8 power factor at 0 . 5 , 0 . 75 , and 1 . 0 - times generator capacity . • Include generator efficiency at 0 . 8 power factor at 0 . 5 , 0 . 75 -, and 1 . 0 - times generator capacity . • Include airflow requirements for cooling and combustion air in cubic feet per minute ( cubic meters per minute ) at 0 . 8 power factor , with air - supply temperature of 95 , 80 , 70 , and 50 deg F ( 35 , 27 , 21 , and 10 deg C ). Provide Drawings indicating requirements and limitations for location of air intake and exhausts . • Include generator characteristics , including , but not limited to , kilowatt rating , efficiency , reactance ’ s , and short - circuit current capability . WARRANTY • Manufacturer ' s Warranty : Manufacturer agrees to repair or replace components of packaged engine generators and associated auxiliary components that fail in materials or workmanship within specified warranty period . • Warranty Period : 5 years from date of Substantial Completion . PERFORMANCE REQUIREMENTS • Seismic Performance : Engine generator housing , subbase fuel tank , US engine generator , batteries , battery racks , silencers , sound attenuating equipment , accessories , and components shall withstand the effects of earthquake motions determined according to ASCE / SEI 7 . • The term " withstand " means “ the unit will remain in place without separation of any parts when subjected to the systemic forces specified and the unit will be fully operational after the systemic event .” • Component Importance factor : 1 . 5 . • B11 Compliance : Comply with B11 . 19 . • NFPA Compliance : Comply with NFPA 37 . • Comply with NFPA 70 . • Comply with NFPA 110 requirements for Level 2 EPSS . • UL Compliance : Comply with UL 2200 . • Engine Exhaust Emissions : Comply with EPA Tier 3 requirements and applicable state and local government requirements . • Noise Emission : Comply with applicable state and local government requirements for maximum noise level at 71dBA at 23 feet due to sound emitted by engine generator including engine , engine exhaust , engine cooling - air intake and discharge , and other components of installation . • Environmental Conditions : Engine generator system shall withstand the following environmental conditions without mechanical or electrical damage or degradation of performance capability : Ambient Temperature : 5 to 104 deg F . • Relative Humidity : Zero to 95 percent . • Altitude : Sea level to 1000 feet . ENGINE GENERATOR ASSEMBLY DESCRIPTION • Factory - assembled and - tested , water - cooled engine , with brushless generator and accessories . • Electrical Components , Devices , and Accessories : Listed and labeled as defined in NFPA 70 , by a qualified testing agency , and marked for intended location and use . • Power Rating : Standby • EPSS Class : Engine generator shall be classified as a Class 33 according to NFPA 110 . • Service Load : 313 kVA . • Power Factor : 0 . 8 , lagging . • Frequency : 60 Hz . • Voltage : 480Y / 277V . • Phase : Three - phase , four wire , wye . • Induction Method : Turbocharged and aftercooled . • Governor : Adjustable isochronous , with speed sensing . • Mounting Frame : Structural steel framework to maintain alignment of mounted components without depending on concrete foundation . Provide lifting attachments sized and spaced to prevent deflection of base during lifting and moving . Rigging Diagram : in Submittal to indicate location and lifting capacity of each lifting attachment and engine generator center of gravity . • Capacities and Characteristics : Power Output Ratings : Nominal ratings as indicated at 0 . 8 power factor excluding power required for the continued and repeated operation of the unit and auxiliaries . • Nameplates : For each major system component to identify . DIESEL ENGINE • Fuel : ASTM D975 , diesel fuel oil , Grade 2 - D S15 . Diesel No . 2 . Or approved renewable diesel fuel replacement . • Rated Engine Speed : 1800 rpm . • Lubrication System : Skid - mounted . Filter and Strainer : Rated to remove 90 percent of particles 5 micrometers and smaller while passing full flow . • Thermostatic Control Valve : Control flow in system to maintain optimum oil temperature . Unit shall be capable of full flow and is designed to be fail - safe . • Crankcase Drain : Arranged for complete gravity drainage to an easily removable container with no disassembly and without use of pumps , siphons , special tools , or appliances .

Location

Country

United States of America (USA)

State

California

Source

Source

California Purchasing Group

URL

More Details

Record type

Tender

Sector

Water Supply and Storage, Energy Storage, Steel, Cement, Geothermal, Manufacturing (Industrial), Oil and Gas, Power Generation (CCGT), Government