RFI Questions and VA Responses 528A6-19-604 Renovate B76 6th floor Solicitation #: 36C24226B0048 RFI 6: DWG M202 Per keynote 5 we are to install steam drip trap. Please indicate what detail is to be used for this note and if this line is intended for future use and capped or is to be tied back into steam condensate system RFI 6 VA Response: Tie it back to steam condensate system. RFI 7: Do we happ

Status
Prospective
Sector
Commercial, Residential, Cement
Location
United States of America
Updated
3 Nov 2026
Source
SAM.gov

ConstructChat

Ask ConstructChat about Y1Da--528A6-19-604 Renovate B76 6Th Floor

Pick a question to edit it, or write your own.

First answer free · no account

I am a

Tender Information FAQ

Tender Information

3 Q
The tender “Y1Da--528A6-19-604 Renovate B76 6Th Floor” is a tender record in Taiyo, linked to the Commercial sector. It is issued for works, goods, or services related to United States of America.

Participants

Not available for this record.

Status

Original status

solicitation

Taiyo status

Prospective

Taiyo last update

2026-11-03

Contact

Not available for this record.

Description

Description

RFI Questions and VA Responses 528A6-19-604 Renovate B76 6th floor Solicitation #: 36C24226B0048 RFI 6: DWG M202 Per keynote 5 we are to install steam drip trap. Please indicate what detail is to be used for this note and if this line is intended for future use and capped or is to be tied back into steam condensate system RFI 6 VA Response: Tie it back to steam condensate system. RFI 7: Do we happen to know who has the Speaker/PA system so I can reach out to them for new speakers and such to match the existing system RFI 7 VA Response: Avaya is one supplier that is utilized on station. RFI 8: Regarding the tile to be removed/replaced on the 5th floor shown on A111: Normally, if the old plaster ceiling above contains Asbestos-Containing Material (ACM), we assume the dust on top of the existing ceiling tiles is also hazardous. Should this be presumed to perform demolition under containment conditions? RFI 8 VA Response: Yes Containment conditions will need to be provided as and when required by the applicable regulations. RFI 9: The documents show the 6th floor deck is 75 -9 ¼ , but we can t confirm that the first floor is 0 -0 datum. Can you provide any additional details regarding overall elevations? RFI 9 VA Response: The documentation shows the 7th floor (attic floor) to be 75 -9 ¼ , sixth floor decking is approximately 65 from first floor RFI 10: Will the VA allow elevator use to move materials to the 6th floor. RFI 10 VA Response: The VA will allow elevator use to move new materials and construction equipment. RFI 11: In regard to drawings ASB-01 - General Note 1 states there is floor tile / mastic removal in rooms 611, 619, 613, 615, 615A, 617, and 623 - however on my prints three rooms are only indicated as work area for tile / mastic abatement. I tried referencing G-102 but the room numbers are not listed.  RFI 11 VA Response: Please refer to the following ASB-01 representation, RFI 12: On drawings ASB-01 - General Note 15 - states ACM glue is present on ceilings on the 5th floor - G102 shows that there is work above ceiling on the 5th floor? Will this area be a part of the abatement scope? There is no mention of removal other than general note 15 - stating that acm is present on the floor. RFI 12 VA Response: ASB-01 identifies 6th floor abatement areas. General note 15 is a safety awareness note for demolition and reinstall new connections at the riser for plumbing and mechanicals. ACM is present in the corridor ceiling of the fifth floor. Additional abatement to the fifth floor is not required. Please refer to the following ASB-01 representation, RFI 13: Is the subfloor a concrete base or wood? RFI 13 VA Response: Concrete RFI 14: Is an infra-red heating unit mandatory for floor tile removal? Referencing section 028213 - 19 - 52 section 4. RFI 14 VA Response: Yes

Original sector

Construction

Location

Country

United States of America (USA)

Source

Source

SAM.gov

URL

More Details

Record type

Tender

Sector

Commercial, Residential, Cement

Article published date

2026-04-29

More on this tender

Research

Free account

View all details

You are reading the public part. A free account opens the rest:

  • Every detail on this tender
  • News and media coverage
  • Technical research
View all details

Free account · no card · lands you back on this tender