36C24226R0060 Amendment 5 630A4-26-401 MRI AHU Modification 8. Question -Hallway Fan Coil Units-The contract documents indicate (6) 18,000 BTU/h chilled water surface-mounted fan coil units in the hallway. We have concerns with this configuration: the surface-mounted units would protrude into the corridor, presenting both an aesthetic issue and a potential head-strike hazard for pedestrians. We pr

Status
Prospective
Sector
Residential, Water Supply and Storage, Commercial
Location
United States of America
Updated
3 Nov 2026
Source
SAM.gov

ConstructChat

Ask ConstructChat about Y1Da--630A4-26-401 Mri Ahu Modification

Pick a question to edit it, or write your own.

First answer free · no account

I am a

Tender Information FAQ

Tender Information

3 Q
The tender “Y1Da--630A4-26-401 Mri Ahu Modification” is a tender record in Taiyo, linked to the Residential sector. It is issued for works, goods, or services related to United States of America.

Participants

Not available for this record.

Status

Original status

solicitation

Taiyo status

Prospective

Taiyo last update

2026-11-03

Contact

Not available for this record.

Description

Description

36C24226R0060 Amendment 5 630A4-26-401 MRI AHU Modification 8. Question -Hallway Fan Coil Units-The contract documents indicate (6) 18,000 BTU/h chilled water surface-mounted fan coil units in the hallway. We have concerns with this configuration: the surface-mounted units would protrude into the corridor, presenting both an aesthetic issue and a potential head-strike hazard for pedestrians. We propose substituting ceiling-mounted fan coil units in lieu of the surface-mounted units. Please advise which of the following options is acceptable: VA Response: Option A would be acceptable if there is no additional cost to the VA. Six ceiling mounted units would provide both the desired level of equipment redundancy and distributed air flow equivalent to the contract design wall mounted units. An 18,000 btu wall mounted evaporator fan unit requires a minimum of 6 inches of clearance below the ceiling for proper air flow. As the evaporator fan coil unit is approximately 12-14 inches high, in an 8 foot high corridor (96 inches clear), there would be a minimum of 76 inches clearance under the evaporator fan unit, or 6 foot 3 inches. If the corridor is higher than 8 feet then the clearance would increase. Option A: Provide (6) ceiling-mounted fan coil units at 18,000 BTU/h each; note that due to ceiling constraints, the units cannot be equally spaced along the corridor. Option B: Provide (3) ceiling-mounted fan coil units of higher capacity, sized to provide equivalent total cooling capacity, spaced evenly along the corridor.

Original sector

Construction

Location

Country

United States of America (USA)

Source

Source

SAM.gov

URL

More Details

Record type

Tender

Sector

Residential, Water Supply and Storage, Commercial

Article published date

2026-08-27

More on this tender

Research

Free account

View all details

You are reading the public part. A free account opens the rest:

  • Every detail on this tender
  • News and media coverage
  • Technical research
View all details

Free account · no card · lands you back on this tender